Why you should choose KRLs FO device?
Nominal power: | from 100 kvar to 400 kvar |
Nominal voltage: | 400 V |
Max. voltage: | 1.1 Un |
Step power: | 3.125 ; 6.25 ; 12.5 ; 25 ; 50 |
Mains frequency: | 50 Hz |
Protection class: | IP 20, outdoor version IP 54 |
Ambient temperature: | -20...+40°C "D" temperature class |
Capacitors: | Electronicon, MKPg 3 phase, Un=440 V (7%), Un=525 V (14%) PCB free |
Discharge resistors: | Internally connected |
Controller: | Microprocessor controlled, with continuous digital cosφ display |
Contactors: | Special capacitor contactors |
Cooling requirements: | Air-cooling 950 m3/h, Ambient temperature +7°C |
Cabinet: | Standing cabinet 2000 x 800 x 600 mm (h x w x d) RAL 7035 light grey |
Dielectric loss by detuning PFC: | ≤ 5 W/kvar |
Target cosφ: | 0.5 capacitive and 0.5 inductive digitally adjustable |
Detuning reactors: | Harmonic filter reactors with temperature switch |
Detuning frequency | 134 Hz (p=14%) ; 189Hz (p=7%) |
Current transformer signal: | CT.../5A |
Voltage signal: | Internally connected |
Relevant standards: | EN61439-1, EN61439-2, IEC 61921 IEC 60831, VDE 560, IEC 439/1–2 |
TÜV certificate number: | MK 69249379 0001 |
Are you interested in our product?